In electrical engineering utilization categories are defined by IEC standards[1] and indicate the type of electrical load and duty cycle of the loads to ease selection of contactors and relays.
Utilization Category | Typical Application[2] | Applicable IEC norm |
---|---|---|
AC-1 | Non-inductive or slightly inductive loads, example: resistive furnaces, heaters | 60947-4-1 |
AC-2 | Slip-ring motors: switching off | 60947-4-1 |
AC-3 | Squirrel-cage motors: starting, switches off motors during running time | 60947-4-1 |
AC-4 | Squirrel-cage motors: starting, plugging, inching | 60947-4-1 |
AC-5a | Switching of discharge lamps | 60947-4-1 |
AC-5b | Switching of incandescent lamps | 60947-4-1 |
AC-6a | Switching of transformers | 60947-4-1 |
AC-6b | Switching of capacitor banks | 60947-4-1 |
AC-7a | Slightly inductive loads in household appliances: examples: mixers, blenders | 60947-4-1 61095 |
AC-7b | Motor-loads for household appliances: examples: fans, central vacuum | 60947-4-1 61095 |
AC-8a | Hermetic refrigerant compressor motor control with manual resetting overloads | 60947-4-1 |
AC-8b | Hermetic refrigerant compressor motor control with automatic resetting overloads | 60947-4-1 |
AC-12 | Control of resistive loads and solid state loads with opto-coupler isolation | 60947-5-2 |
AC-13 | Control of solid state loads with transformer isolation | 60947-5-1 |
AC-14 | Control of small electromagnetic loads | 60947-5-1 |
AC-15 | Control of A.C. electromagnetic loads | 60947-5-1 |
AC-20 | Connecting and disconnecting under no-load conditions | 60947-3 |
AC-21 | Switching of resistive loads, including moderate overloads | 60947-3 |
AC-22 | Switching of mixed resistive and inductive loads, including moderate overloads | 60947-3 |
AC-23 | Switching of motor loads or other highly inductive loads | 60947-3 |
A | Protection of circuits, with no rated short-time withstand current | 60947-3 |
B | Protection of circuits, with a rated short-time withstand current | 60947-3 |
DC-1 | Non Inductive or slightly inductive loads, resistance furnaces, heaters | 60947-4-1 |
DC-3 | Shunt-motors, starting, plugging(1), inching(2), dynamic braking of motors | 60947-4-1 |
DC-5 | Series-motors, starting, plugging(1), inching(2), dynamic braking of motors | 60947-4-1 |
DC-6 | Switching of incandescent lamps | 60947-4-1 |
DC-12 | Control of resistive loads and solid state loads with opto-coupler isolation | 60947-5-1 60947-5-2 |
DC-13 | Control of D.C. electromagnetics | 60947-5-1 60947-5-2 |
DC-14 | Control of D.C. electromagnetic loads having economy resistors in the circuit | 60947-5-1 |
DC-20 | Connecting and disconnecting under no-load conditions | 60947-5-1 |
DC-21 | Switching of resistive loads, including moderate overloads | 60947-5-1 |
DC-22 | Switching of mixed resistive and inductive loads, including moderate overloads (i.e. shunt motors) | 60947-5-1 |
DC-23 | Switching of highly inductive loads (i.e. series motors) | 60947-5-1 |