In electrical engineering utilization categories are defined by IEC standards[1] and indicate the type of electrical load and duty cycle of the loads to ease selection of contactors and relays.

Utilization Category Typical Application[2] Applicable IEC norm
AC-1 Non-inductive or slightly inductive loads, example: resistive furnaces, heaters 60947-4-1
AC-2 Slip-ring motors: switching off 60947-4-1
AC-3 Squirrel-cage motors: starting, switches off motors during running time 60947-4-1
AC-4 Squirrel-cage motors: starting, plugging, inching 60947-4-1
AC-5a Switching of discharge lamps 60947-4-1
AC-5b Switching of incandescent lamps 60947-4-1
AC-6a Switching of transformers 60947-4-1
AC-6b Switching of capacitor banks 60947-4-1
AC-7a Slightly inductive loads in household appliances: examples: mixers, blenders 60947-4-1
61095
AC-7b Motor-loads for household appliances: examples: fans, central vacuum 60947-4-1
61095
AC-8a Hermetic refrigerant compressor motor control with manual resetting overloads 60947-4-1
AC-8b Hermetic refrigerant compressor motor control with automatic resetting overloads 60947-4-1
AC-12 Control of resistive loads and solid state loads with opto-coupler isolation 60947-5-2
AC-13 Control of solid state loads with transformer isolation 60947-5-1
AC-14 Control of small electromagnetic loads 60947-5-1
AC-15 Control of A.C. electromagnetic loads 60947-5-1
AC-20 Connecting and disconnecting under no-load conditions 60947-3
AC-21 Switching of resistive loads, including moderate overloads 60947-3
AC-22 Switching of mixed resistive and inductive loads, including moderate overloads 60947-3
AC-23 Switching of motor loads or other highly inductive loads 60947-3
A Protection of circuits, with no rated short-time withstand current 60947-3
B Protection of circuits, with a rated short-time withstand current 60947-3
DC-1 Non Inductive or slightly inductive loads, resistance furnaces, heaters 60947-4-1
DC-3 Shunt-motors, starting, plugging(1), inching(2), dynamic braking of motors 60947-4-1
DC-5 Series-motors, starting, plugging(1), inching(2), dynamic braking of motors 60947-4-1
DC-6 Switching of incandescent lamps 60947-4-1
DC-12 Control of resistive loads and solid state loads with opto-coupler isolation 60947-5-1
60947-5-2
DC-13 Control of D.C. electromagnetics 60947-5-1
60947-5-2
DC-14 Control of D.C. electromagnetic loads having economy resistors in the circuit 60947-5-1
DC-20 Connecting and disconnecting under no-load conditions 60947-5-1
DC-21 Switching of resistive loads, including moderate overloads 60947-5-1
DC-22 Switching of mixed resistive and inductive loads, including moderate overloads (i.e. shunt motors) 60947-5-1
DC-23 Switching of highly inductive loads (i.e. series motors) 60947-5-1

See also

NEMA contact ratings