Sweep frequency response analysis

From Wikipedia, the free encyclopedia
This is an old revision of this page, as edited by 49.248.39.202 (talk) at 04:47, 21 August 2014. The present address (URL) is a permanent link to this revision, which may differ significantly from the current revision.

Sweep Frequency Response Analysis (SFRA) is a powerful and sensitive= method[according to whom?] to evaluate the mechanical integrity of core, windings and clamping structures within power transformers by measuring their electrical transfer functions over a wide frequency range. SFRA is a proven method for frequency measurements.[citation needed]

Methods

The SFRA is a comparative method, meaning an evaluation of the transformer condition is done by comparing an actual set of SFRA results to reference results. Three methods are commonly used to assess the measured traces:

  • Time-based – current SFRA results will be compared to previous results of the same unit.
  • Type-based – SFRA of one transformer will be compared to an equal type of transformer.
  • Phase comparison – SFRA results of one phase will be compared to the results of the other phases of the same transformer.

How SFRA works

Transformers consist of multiple complex networks of capacitances and resistors that can generate a unique signature when tested at discreet frequencies and plotted as a curve. The distance between conductors of the transformer forms a capacitance. Any movement of the conductors or windings will change this capacitance. This capacitance being a part of complex L (inductance), R (Resistance) and C (Capacitance) network, any change in this capacitance will be reflected in the curve or signature.

An initial SFRA test is carried out to obtain the signature of the transformer frequency response by injecting various discreet frequencies. This reference is then used for future comparisons. A change in winding position, degradation in the insulation, etc. will result in change in capacitance or inductance thereby affecting the measured curves.

Tests are carried out periodically or during major external events like short circuits and results compared against the initial signature to test for any problems. The basic functionality of SFRA supports following measuring modes. Voltage transfer function Uo/Ui (f) SFRA test reveals if the transformers mechanical or electrical integrity has been compromised.

Problems that can be detected

SFRA analysis can detect problems in transformers such as:

  • winding deformation – axial & radial, like hoop buckling, tilting, spiraling
  • displacements between high and low voltage windings
  • partial winding collapse
  • shorted or open turns
  • faulty grounding of core or screens
  • core movement
  • broken clamping structures
  • problematic internal connections

Uses

  • To obtain initial signature of healthy transformer for future comparisons
  • Periodic checks as part of regular maintenance
  • Immediately after a major external event like short circuit
  • Transportation or relocation of transformer
  • Earthquakes
  • Pre-commissioning check

SFRA kits

  • Doble: M5200/M5400 Sweep Frequency Response Analyzer
  • Megger: FRAX99/101/150 Sweep Frequency Response Analyzer
  • Newtons4th: SFRA45 Sweep Frequency Response Analyzer
  • Omicron: VE000660 SFRA analyzer complete set
  • SIVA Instrument: Sweep Frequency Response Analyzer
  • Core Technology: Sweep Frequency Response Analyzer