Utilization categories
Appearance
Utilization categories are defined by IEC standards and indicated the type of loads and duty cycle of the loads to ease selection of contactors and relays.[1]
Utilization Category | Type of Application[2]
"|- |
AC-1 | Non Industive or slightly inductive loads, example: resistive furnaces, Heaters"
"|- |
AC-2 | Slip-ring motors: switching off"
"|- |
AC-3 | Squirrel-cage motors: starting, swithces off motors during running time"
"|- |
AC-4 | Squirrel-cage motors: starting, plugging (1), inching (2)"
"|- |
AC-5a | Switching of electric discharge lamps"
"|- |
AC-5b | Switching of incandescent lamps"
"|- |
AC-6a | Switching of transfomers"
"|- |
AC-6b | Switching of capacitor banks"
"|- |
AC-7a | Slightly inductive loads in household appliances: examples: mixers, blenders"
"|- |
AC-7b | Motor-loads for household appliances: examples: fans, central vacuum"
"|- |
AC-8a | Hermetic refrigerant compressor motor control with manual resetting overloads"
"|- |
AC-8b | Hermetic refrigerant compressor motor control with automatic resetting overloads"
"|- |
AC-12 | Control of resisitive loads and solid state loads with opto-coupler isolation"
"|- |
AC-13 | Control of solid state loads with transformer isolation"
"|- |
AC-14 | Control of small electromagnetic loads"
"|- |
AC-15 | Control of A.C. electromagnetic loads"
"|- |
AC-20 | Connecting and disconnecting under no-load conditions"
"|- |
AC-21 | Switching of resistive loads, including moderate loads"
"|- |
AC-22 | Switching of mixed resistive and inductive loads, including moderate overloads"
"|- |
AC-23 | Switching of motor loads or other highly inductive loads"
"|- |
A | Protection of circuits, with no rated short-time withstand current"
"|- |
B | Protection of circuits, with a rated short-time withstand current"
"|- |
DC-1 | Non Inductive or slightly inductive loads, resistance furnaces, heaters"
"|- |
DC-3 | Shunt-motors, starting, plugging(1), inching(2), dynamic breaking of motors"
"|- |
DC-5 | Series-motors, starting, plugging(1), inching(2), dynamic breaking of motors"
"|- |
DC-6 | Switching of incandescent lamps"
"|- |
DC-12 | Control of resistive loads and solid state loads with opto-coupler isolation"
"|- |
DC-13 | Control of D.C. electromagnetics"
"|- |
DC-14 | Control of D.C. electromagnetic loads having economy resistors in the circuit"
"|- |
DC-20 | Connecting and disconnecting under no-load conditions"
"|- |
DC-21 | Switching of resistive loads, including moderate overloads"
"|- |
DC-22 | Switching of mixed resistive and inductive loads, including moderate overloads (i.e. shunt motors)"
"|- |
DC-23 | Switching of highly inductive loads (i.e. series motors)" |
---|