Cleveland open-cup method
The Cleveland open cup method is one of three main methods in chemistry for determining the flash point of a petroleum product using a Cleveland open cup apparatus or Cleveland open cup tester. First, the test cup of the apparatus (usually brass) is filled to a a certain level with a portion of the product. Then, the temperature of this chemical is increased rapidly and then at a slow, constant rate as it approaches the theoretical flash point. The increase in temperature will cause the chemical to begin to produce flammable vapor in increasing quantities and density. The lowest temperature at which a small test flame passing over the surface of the liquid and causing it to ignite is considered the chemical's flash point. This apparatus may also be used to determine the chemical's fire point which is considered to have been reached when the application of the test flame produces 5 seconds of ignition.[1]
The other principal methods are the Pensky-Martens closed cup method and the Tagliabue cup method (often called simply the "Tag method").
References
- ^ Manual on flash point standards and their use: methods and regulations. Baltimore, MD: ASTM International. September 1992. ISBN 0803114109.