Limiting oxygen concentration
Limiting oxygen concentration, (LOC)[1], also known as the Minimum oxygen concentration, (MOC)[2], is defined as the limiting concentration of oxygen below which combustion is not possible, independent of the concentraion of fuel. It is expressed in units of volume percent of oxygen. The LOC varies with pressure and temperature. It is also dependent on the type of inert (non-flammable) gas.
Gas or vapor | Nitrogen / Air | Carbon dioxide / Air |
Hydrogen | 5 | 5.2 |
Methane | 12 | 14.5 |
Ethane | 11 | 13.5 |
Propane | 11.5 | 14.5 |
n-Butane | 12 | 14.5 |
Isobutane | 12 | 15 |
The effect of increasing the concentraion of inert gas can be understood by viewing the inert as thermal ballast that quenches the flame temperature to a level below which the flame cannot exist.[4]. Carbon dioxide is therefore more effective than nitrogen due to its higher molar heat capacity[5]
The concept has important practical use in fire safety engineering. For instance, to safely fill a new container or a pressure vessel with flammable gasses, the atmosphere of normal air (containing about 21 volume percent of oxygen) in the vessel would first be flushed (purged) with nitrogen or another non-flammable inert gas, thereby reducing the oxygen concentration inside the container. When the oxygen concentration is below the LOC, flammable gas can be safely admitted to the vessel because the possibility of internal explosion has been eliminated.
See also
Sources
Monographs
- Green, Don W. (October 23). Perry's Chemical Engineers' Handbook. McGraw-Hill Professional; 8 edition. ISBN 0071422943.
{{cite book}}
: Check date values in:|date=
and|year=
/|date=
mismatch (help); Unknown parameter|coauthors=
ignored (|author=
suggested) (help) Chapter 23
- Drysdale, Dougal (1985). An Introduction to Fire Dynamics. Wiley. ISBN 0 471 90613 1.
{{cite book}}
: Cite has empty unknown parameter:|coauthors=
(help)
References'