Open-circuit saturation curve
![]() | This article is actively undergoing a major edit for a little while. To help avoid edit conflicts, please do not edit this page while this message is displayed. This page was last edited at 04:19, 8 July 2023 (UTC) (22 months ago) – this estimate is cached, . Please remove this template if this page hasn't been edited for a significant time. If you are the editor who added this template, please be sure to remove it or replace it with {{Under construction}} between editing sessions. |

The open-circuit saturation curve (also open-circut characteristic, OCC) of a synchronous generator is a plot of the output voltage as a function of the excitation current or field.[1]
At the low field, the permeable iron in the magnetic circuit of the generator is not saturated, therefore the reluctance almost entirely depends on the fixed contribution of the air gap, so the part of the curve that starts at the point of origin is a linear "air-gap line" (output voltage is proportional to the excitation current). As the iron saturates with higher excitation and thus higher magnetic flux, the reluctance increases, and the OCC deflects down from the air-gap line.[1]
The curve is obtained by rotating the generator at the rated RPM with the output terminals disconnected and the output voltage typically going to at least 120% of the rated for the device. The hydraulic units sometimes have to be tested at lower RPM with the resulting voltage scaled up to accommodate the differences in frequency. Since the test goes above the rated voltage, the step-up transformer is typically also disconnected to avoid damaging it.[2]
References
- ^ a b Klempner & Kerszenbaum 2004, p. 125.
- ^ Boldea 2015, p. 412.
Sources
- Klempner, G.; Kerszenbaum, I. (2004). "Open-Circuit Saturation Characteristic". Operation and Maintenance of Large Turbo-Generators. IEEE Press Series on Power Engineering. Wiley. ISBN 978-0-471-61447-0. Retrieved 2023-07-08.